Housing powder-coated steel plate, color RAL 7043 (traffic grey B)
Technical data:
Model FlowCool Unicus
Eff. cooling capacity *
Operating range cooling temperature
Operating range ambient temperature
Temperature constancy
Rated coolant flow **
Pump type
Pump pressure ***
Tank capacity
Water connection, hose olives
Power input max.
Operating voltage
Weight
Dimensions (W × D × H)
Catalogue number
kW :
kW :
°C :
°C :
m³/h :
:
bar :
L :
:
kW :
:
kg :
mm :
:
FCUN 015
15.8
+10 / +50
+2 / +40
±2
2.7
P3-AR02B
2.7
30
G1½"
0.6
3/N/PE ~ 400 V 50 Hz
109
580 × 650 × 845
GUFCUN015-NEB
FCUN 024
24.4
+10 / +50
+2 / +40
±2
4.2
P3-AR02B
2.2
30
G1½"
0.6
3/N/PE ~ 400 V 50 Hz
111
580 × 650 × 845
GUFCUN024-NEB
* at ΔT = 5 K between in-house cooling circuit and application cooling circuit. ** at ΔT = 5 K in the application cooling circuit between feed and return. *** Pump pressure at rated coolant flow.
Additional options and accessories
FlowCool Unicus options / accessories
Cat.No.
Pumpe P4-AS22B instead of P3-AR02B (3/N/PE ~ 400V 50Hz)
MFCUN6-P4-AS22B-024
Pumpe P8-AN09B instead of P3-AR02B (3/N/PE ~ 400V 50Hz)
MFCUN6-P8-AN09B-024
Continuous-flow system without tank and / or without pump
on request
Automatic by-pass valve
ZFCUN6-041-024
4 swivel castors, 2 with brakes
YFCUN5-021-024
Export version with special voltages / frequencies