Intelligent
Recirculating Chillers
Air-to-Water Heat Exchanger System
AirCool Ventus ACVE 090 to ACVE 150
Cooling capacity 89.6 kW to 605 kW
AirCool Ventus with option color RAL 7043 (traffic grey B)
Standard design
- Single circuit system including tank open to atmosphere
- Without active refrigeration
- Heat discharged into ambient air
- Plastic tank with water level indicator
- Electronic microprocessor-controlled thermostat with digital display
- Error messages dislpayed as individual codes by controller
- Remote control
- Control cabinet with main switch
- Built-in Pump (see pump characteristics)
- Housing powder coated, colour RAL 7035 (lightgrey)
- Due to process employed, the exit temperature of the cooling medium is always above the ambient temperature
- Suitable for industrial use
- Absolutely reliable design
- Contains all the components required for the fully automatic cooling process
Technical data:
Model AirCool Ventus
Cooling capacity * at ΔT = 5 K / 20 K
Cooling medium
Rated coolant flow
Pump type
Pump pressure **
Tank capacity
Water connection, female
Required flow of cooling air
Power input max.
Operating voltage
Weight
Dimensions (W × D × H)
Catalogue number
kW :
:
m³/h :
:
bar :
L :
:
m³/h :
kW :
:
kg :
mm :
:
ACVE090
89.6 / 358
Wasser / water
15.4
P3-AP04B
2.8
200
G3"
44000
6.0
3/N/PE ~ 400 V 50 Hz
1391
3990 × 1525 × 2170
GUACVE090-NEB
ACVE120
116 / 465
Wasser / water
20.0
P3-AP04B
2.5
200
G3"
48000
6.0
3/N/PE ~ 400 V 50 Hz
1454
3990 × 1525 × 2170
GUACVE120-NEB
ACVE150
151 / 605
Wasser / water
26.0
P2-AP13B
2.0
200
G3"
69000
7.9
3/N/PE ~ 400 V 50 Hz
1496
3990 × 1525 × 2170
GUACVE150-NEB
* Above the current ambient temperature.
** Pump pressure at rated coolant flow.
Additional options and accessories
AirCool Ventus options / accessories |
Cat.No. |
Pump P5-AP06B instead of P3-AP04B (3/N/PE ~ 400V 50Hz) |
MACVE6-P5-AP06B-090 |
Pump P7-AP08B instead of P3-AP04B (3/N/PE ~ 400V 50Hz) |
MACVE6-P7-AP08B-090 |
Pump P5-AP07B instead of P3-AP04B (3/N/PE ~ 400V 50Hz) |
MACVE6-P5-AP07B-120 |
Pump P8-AP09B instead of P3-AP04B (3/N/PE ~ 400V 50Hz) |
MACVE6-P8-AP09B-120 |
Pump P4-AP16B instead of P2-AP13B (3/N/PE ~ 400V 50Hz) |
MACVE6-P4-AP16B-150 |
Pump P7-AP18B instead of P2-AP13B (3/N/PE ~ 400V 50Hz) |
MACVE6-P7-AP18B-150 |
Water flow switch |
ZACVE6-008-150 |
Continuous-flow system without tank |
on request |
Export version with special voltages / frequencies |
on request |
Additional options and accessories . . .
. . . as well as pump alternatives on
⇒ request
Dimensions and connections
Download Data sheet 6E08
All rights reserved. Changes without notification © National Lab GmbH 2013