Logo National Lab GmbH

Intelligent

Recirculating Chillers

 

Air-to-Water Heat Exchanger System

AirCool Ventus ACVE 090 to ACVE 150
Cooling capacity 89.6 kW to 605 kW

Device 6E08
AirCool Ventus with option color RAL 7043 (traffic grey B)

Standard design

 

Technical data:

Model AirCool Ventus
Cooling capacity * at ΔT = 5 K / 20 K
Cooling medium
Rated coolant flow
Pump type
Pump pressure **
Tank capacity
Water connection, female
Required flow of cooling air
Power input max.
Operating voltage
Weight
Dimensions (W × D × H)
Catalogue number
 
 
kW :
:
m³/h :
:
bar :
L :
:
m³/h :
kW :
:
kg :
mm :
:
 
ACVE090
89.6 / 358
Wasser / water
15.4
P3-AP04B
2.8
200
G3"
44000
6.0
3/N/PE ~ 400 V 50 Hz
1391
3990 × 1525 × 2170
GUACVE090-NEB
 
ACVE120
116 / 465
Wasser / water
20.0
P3-AP04B
2.5
200
G3"
48000
6.0
3/N/PE ~ 400 V 50 Hz
1454
3990 × 1525 × 2170
GUACVE120-NEB
 
ACVE150
151 / 605
Wasser / water
26.0
P2-AP13B
2.0
200
G3"
69000
7.9
3/N/PE ~ 400 V 50 Hz
1496
3990 × 1525 × 2170
GUACVE150-NEB
 
* Above the current ambient temperature.
** Pump pressure at rated coolant flow.

Additional options and accessories

AirCool Ventus options / accessories Cat.No.
Pump P5-AP06B instead of P3-AP04B (3/N/PE ~ 400V 50Hz) MACVE6-P5-AP06B-090
Pump P7-AP08B instead of P3-AP04B (3/N/PE ~ 400V 50Hz) MACVE6-P7-AP08B-090
Pump P5-AP07B instead of P3-AP04B (3/N/PE ~ 400V 50Hz) MACVE6-P5-AP07B-120
Pump P8-AP09B instead of P3-AP04B (3/N/PE ~ 400V 50Hz) MACVE6-P8-AP09B-120
Pump P4-AP16B instead of P2-AP13B (3/N/PE ~ 400V 50Hz) MACVE6-P4-AP16B-150
Pump P7-AP18B instead of P2-AP13B (3/N/PE ~ 400V 50Hz) MACVE6-P7-AP18B-150
Water flow switch ZACVE6-008-150
Continuous-flow system without tank on request
Export version with special voltages / frequencies on request

Additional options and accessories . . .

. . . as well as pump alternatives on   ⇒ request
Diagramm 6E08 Teil 2

Dimensions and connections

Dimensions 6E08

Download Data sheet 6E08

*.PDF
All rights reserved. Changes without notification © National Lab GmbH 2013