Logo National Lab GmbH

Intelligent

Recirculating Chillers

 

Recirculating Chillers

ProfiCool Modulus PCMO 40 to PCMO 50
Cooling capacity 3.2 kW to 5.0 kW

Device 6A26

Standard design

 

Technical data:

Model ProfiCool Modulus
Net. cooling capacity at +20 °C / +15 °C
Eff. cooling capacity at +20 °C / +15 °C
Operating range *
Temperature constancy
Rated coolant flow
Pump type
Pump pressure **
Tank capacity
Water connection, female
Required flow of cooling air
Power input max.
Operating voltage
 
Weight
Dimensions (W × D × H)
Refrigerant, CFC-free
Catalogue number
 
 
kW :
kW :
°C :
°C :
m³/h :
:
bar :
L :
:
m³/h :
kW :
:
:
kg :
mm :
:
:
 
PCMO 35
3.7 / 3.3
3.5 / 3.1
+15 / +30
±2.0**
0.6
P14-ZA23D
3.0
33
G½"
2.300
1.3
3/PE ~ 380-415 V 50 Hz
3/PE ~ 440-460 V 60 H
96
440 × 600 × 800
R407C
GUPCMO0035.01-NEM
 
PCMO 45
4.7 / 4.1
4.5 / 3.9
+15 / +30
±2**
0,77
P14-ZA23D
3.0
33
G¾" Innengewinde
2.500
1.9
3/PE ~ 380-415 V 50 Hz
3/PE ~ 440-460 V 60
100
440 × 600 × 800
R407C
GUPCMO0045.01-NEM
 
PCMO 60
6.2 / 5.3
6.0 / 5.1
+15 / +30
±2**
1.0
P14-ZA23D
3.0
33
G¾" Innengewinde
2.300
2.4
3/PE ~ 380-415 V 50 Hz
3/PE ~ 440-460 V 60
110
440 × 600 × 800
R407C
GUPCMO0060.01-NEM
 
* Set temperature < +15°C and > +30 °C on request
** Pressure at rated coolant flow.

Additional options and accessories

ProfiCool Modulus options / accessories Cat.No.
RS485 interface YPCMO2-019-0050
Continuous flow system without tank and / or without pump on request
Enhancement working range to +5°C MPCMO7-006-0050
Temperature constancy up to ±0.1 °C ZPCMO9-067-0050
Export version with special voltages / frequencies on request

Additional options and accessories . . .

. . . as well as pump alternatives on   ⇒ request

Pump characteristics

Diagramm 6A26

Download Data sheet 6A26

*.PDF
All rights reserved. Changes without notification © National Lab GmbH 2013