Models PCGE 1450, PCGE 1800, PCGE 2100 come with 2 fans
Model PCGE 2600 comes with 3 fans
Technical data:
Model ProfiCool Genius
Net. cooling capacity * at +20 °C / +15 °C
Eff. cooling capacity * at +20 °C / +15 °C
Operating range **
Temperature constancy
Rated coolant flow
Pump type
Pump pressure ***
Tank capacity
Water connection, female
Required flow of cooling air
Starting current
Power input max.
Operating voltage
Weight
Dimensions (W × D × H)
Refrigerant, CFC-free
Catalogue number
kW :
kW :
°C :
°C :
m³/h :
:
bar :
L :
:
m³/h :
A :
kW :
:
kg :
mm :
:
:
PCGE 1450
139.2 / 130.5
140,2 /129,5
+5 / +25
±1.5
22.4
P3-AP51B
3.3
500
/
44.000
212
37.64
< 3/PE ~ 400 V 50 Hz >
1780
3990 × 1325 × 2170
R407C
GUPCGE1450.01-NEB
PCGE 1800
172.8 / 162.0
168.8 / 158.0
+5 / +25
±1.5
27.9
P3-AP51B
3.1
500
G3"
44000
251
46.4
3/N/PE ~ 400 V 50 Hz
1880
3990 × 1325 × 2170
R407C
GUPCGE1800.01-NEB
PCGE 2100
196.8 / 184.5
191.3 / 179.0
+5 / +25
±1.5
31.7
P3-AP34B
3.1
500
G3"
48000
339
52.1
3/N/PE ~ 400 V 50 Hz
1840
3990 × 1325 × 2170
R407C
GUPCGE2100.01-NEB
Model ProfiCool Genius
Net. cooling capacity * at +20 °C / +15 °C
Eff. cooling capacity * at +20 °C / +15 °C
Operating range **
Temperature constancy
Rated coolant flow
Pump type
Pump pressure ***
Tank capacity
Water connection, female
Required flow of cooling air
Starting current
Power input max.
Operating voltage
Weight
Dimensions (W × D × H)
Refrigerant, CFC-free
Catalogue number
kW :
kW :
°C :
°C :
m³/h :
:
bar :
L :
:
m³/h :
A :
kW :
:
kg :
mm :
:
:
PCGE 2600
244.8 / 229.5
239.3 / 224.0
+5 / +25
±1.5
39.5
P3-AP34B
2.9
500
G3"
69000
403
59.0
3/N/PE ~ 400 V 50 Hz
1930
3990 × 1325 × 2170
R407C
GUPCGE2600.01-NEB
* Net. cooling capacity: the heating current that is removed from the coolant inside the evaporator. Eff. cooling capacity: the heating current that the coolant usefully removes. ** Set temperatures < +5 °C and > +25 °C on request. *** Pump pressure at rated coolant flow.
Additional options and accessories
ProfiCool Genius options / accessories
Cat.No.
Pump P5-AP17B instead of P3-AP15B (3/N/PE ~ 400V 50Hz)
MPCGE6-P5-AP17B-1800
Pump P8-AP19B instead of P3-AP15B (3/N/PE ~ 400V 50Hz)
MPCGE6-P8-AP19B-1800
Pump P6-AP18B instead of P3-AP34B (3/N/PE ~ 400V 50Hz)
MPCGE6-P6-AP18B-2100
Pump P8-AP19B instead of P3-AP34B (3/N/PE ~ 400V 50Hz)
MPCGE6-P8-AP19B-2100
Pump P6-AP37B instead of P3-AP34B (3/N/PE ~ 400V 50Hz)
MPCGE6-P6-AP37B-2600
Pump P8-AP39B instead of P3-AP34B (3/N/PE ~ 400V 50Hz)
MPCGE6-P8-AP39B-2600
Continuous-flow system without tank and / or without pump
on request
Overflow by-pass valve
ZPCGE6-041-2600
4 swivel castors, 2 with breaks
ZPCGE5-021-2600
Temperature constancy up to ±0,5 °C
on request
Low ambient temperature kit
MPCGE7-001-2600
Export version with special voltages / frequencies