Logo National Lab GmbH

Intelligent

Recirculating Chillers

 

Recirculating Chillers

ProfiCool Genius PCGE 680 to PCGE 770
Cooling capacity 59 kW to 71 kW

Device 6A07

Standard design

 

Technical data:

Model ProfiCool Genius
Net. cooling capacity * at +20 °C / +15 °C
Eff. cooling capacity * at +20 °C / +15 °C
Operating range **
Temperature constancy
Rated coolant flow
Pump type
Pump pressure ***
Tank capacity
Water connection, female
Required flow of cooling air
Starting current
Power input max.
Operating voltage
Weight
Dimensions (W × D × H)
Refrigerant, CFC-free
Catalogue number
 
 
kW :
kW :
°C :
°C :
m³/h :
:
bar :
L :
:
m³/h :
A :
kW :
:
kg :
mm :
:
:
 
PCGE 680
65.3 / 61.2
63.5 / 59.4
+5 / +25
±1.5
10.5
P3-AR34B
2.6
200
G1½"
15800
156
17.8
3/N/PE ~ 400 V 50 Hz
480
1520 × 1325 × 1525
R407C
GUPCGE0680.01-NEB
 
PCGE 770
71.0 / 66.6
69.2 / 64.8
+5 / +25
±1.5
11.5
P3-AR34B
2.5
200
G1½"
15800
148
20.3
3/N/PE ~ 400 V 50 Hz
510
1520 × 1325 × 1525
R407C
GUPCGE0770.01-NEB
 
* Net. cooling capacity: the heating current that is removed from the coolant inside the evaporator.
   Eff. cooling capacity: the heating current that the coolant usefully removes.
** Set temperatures < +5 °C and > +25 °C on request.
*** Pump pressure at rated coolant flow.

Additional options and accessories

ProfiCool Genius options / accessories Cat.No.
Pump P5-AP06B instead of P3-AR34B (3/N/PE ~ 400V 50Hz) MPCGE6-P5-AP06B-0770
Pump P7-AP08B instead of P3-AR34B (3/N/PE ~ 400V 50Hz) MPCGE6-P7-AP08B-0770
Continuous-flow system without tank and / or without pump on request
Overflow by-pass valve ZPCGE6-041-0770
4 swivel castors, 2 with breaks ZPCGE5-021-0770
Temperature constancy up to ±0,5 °C on request
Low ambient temperature kit MPCGE7-001-0770
Export version with special voltages / frequencies on request

Additional options and accessories . . .

. . . as well as pump alternatives on   ⇒ request

Pump characteristics

Diagramm 6A07

Dimensions and connections

Dimensions 6A07

Download Data sheet 6A07

*.PDF
All rights reserved. Changes without notification © National Lab GmbH 2013